EDR-75

EDR / NDR Series / EDR-75
INDUSTRIAL DIN RAIL SWITCHING POWER SUPPLY

EDR-75

75.6–76.8W DIN Rail Switching Power Supply

Slim industrial DIN rail AC/DC switching power supply available with 12V, 24V and 48V DC output versions for industrial control, automation, electrical cabinets and DIN rail equipment.

EDR-75 DIN rail switching power supply
75.6–76.8W Rated Power Range
12–48V Output Voltage Options
90–264VAC AC Input Range
Up to 88.5% Efficiency
32 × 125.2 × 102 mm Overall Dimensions
PRODUCT OVERVIEW

EDR-75 DIN Rail Power Supply

The EDR-75 Series provides three DC output versions: 12V, 24V and 48V. Rated output power ranges from 75.6W to 76.8W depending on the selected model.

Wide AC Input

90–264VAC or 127–370VDC input range.

Three Output Versions

12V, 24V and 48V DC output options.

Slim DIN Rail Design

32 mm wide enclosure for space-conscious DIN rail installations.

High Efficiency

Efficiency reaches up to 88.5% depending on the selected output model.

OUTPUT SPECIFICATIONS

EDR-75 Model Range

Electrical output specifications for each available voltage version.

Specification EDR-75-12 EDR-75-24 EDR-75-48
DC Voltage 12V 24V 48V
Rated Current 6.3A 3.2A 1.6A
Current Range 0–6.3A 0–3.2A 0–1.6A
Rated Power 75.6W 76.8W 76.8W
Ripple & Noise 80mVp-p 120mVp-p 150mVp-p
Voltage Adjustment Range 12–14V 24–28V 48–55V
Voltage Accuracy ±2.0% ±1.0% ±1.0%
Line Regulation ±0.5% ±0.5% ±0.5%
Load Regulation ±1.0% ±1.0% ±1.0%
Efficiency 85.5% 87.5% 88.5%
Overvoltage Protection 14–17V 29–33V 56–65V
TECHNICAL DATA

General Specifications

Input

Voltage Range 90–264VAC / 127–370VDC
DC Input DC input operation available by connecting AC/L (+) and AC/N (-).
Frequency Range 47–63Hz
AC Current 1.45A / 115VAC, 0.9A / 230VAC
Inrush Current 20A / 115VAC, 35A / 230VAC, cold start
Leakage Current < 1mA / 240VAC

Timing

Setup / Rise Time 1200ms / 60ms at 230VAC; 2000ms / 60ms at 115VAC, at full load
Hold-up Time 60ms at 230VAC; 12ms at 115VAC, at full load

Environment

Working Temperature -20°C to +60°C
Working Humidity 20–95% RH, non-condensing
Storage Temperature / Humidity -40°C to +85°C, 10–95% RH, non-condensing
Temperature Coefficient ±0.03% / °C (0–50°C)
Vibration 10–500Hz, 5G, 10 min/cycle; X, Y and Z axes, 60 min each
Overvoltage Category Category II according to EN61558, EN50178, EN60664-1 and EN62477-1; operating altitude up to 2000 m

Safety & Mechanical

Withstand Voltage I/P–O/P: 3KVAC; I/P–FG: 2KVAC; O/P–FG: 0.5KVAC
Isolation Resistance I/P–O/P, I/P–FG, O/P–FG: 100MΩ / 500VDC / 25°C / 70% RH
MTBF ≥ 506.6K hrs, MIL-HDBK-217F (25°C)
Dimensions 32 × 125.2 × 102 mm
Packaging 0.51kg; 28pcs / 15.3kg / 1.22CUFT

Safety Standards

Safety Norms UL60950-1;
TUV EN60950-1;
EN60335-1;
EN61558-1/-2-16;
CCC GB4943.1;
BSMI CNS14336-1;
EAC TC TP 004;
AS/NZS 60950.1 (by CB)

EMC

EMC Emission EN55022 (CISPR22) Class A;
EN61000-3-2;
EN61000-3-3
EMC Immunity EN61000-4-2,3,4,5,6,8,11;
EN55024;
EN61000-6-2 (EN50082-2);
Class A heavy industrial environment
PROTECTION

Built-in Protection Functions

Overload Protection

Protection operates at approximately 105%–130% of rated output power. Constant current limiting protection is used and the power supply automatically recovers after the abnormal load condition is removed.

Overvoltage Protection

Overvoltage protection turns off the output voltage. Protection levels are 14–17V for the 12V model, 29–33V for the 24V model and 56–65V for the 48V model. Recovery is achieved after restarting the power supply.

Over Temperature Protection

The output is shut down when the over-temperature protection is activated. Recovery is achieved after restarting the power supply.

MECHANICAL DIMENSIONS

EDR-75 Dimension Drawing

Slim industrial DIN rail enclosure and mounting dimensions.

EDR-75 mechanical dimension drawing
Overall Size: 32 × 125.2 × 102 mm
DIMENSIONS IN MILLIMETERS
APPLICATIONS

Typical Applications

Industrial Automation Automation equipment and production control systems.
Control Cabinets DIN rail power supply for industrial electrical panels.
PLC Systems Stable DC power for programmable control equipment.
Industrial Equipment Equipment requiring 12V, 24V or 48V DC power.

Need a Quote for EDR-75?

Tell us the required output voltage, quantity and application. Our team will assist with EDR-75 model selection and quotation.

Request A Quote →
D